Anges Air cooled industrial chiller
-CE ISO9001:2008
-Cooling capacity: 109.6kw 31.16ton
-Double compressors: Danfoss-Performer.
-Dimension: 2000*1560*1880mm
Technical Parameter of Industry Air Cooled Chiller
Model Item | AC-40(D) | |
nominal cooling capacity | kcal/h | 94256 |
kw | 109.6 | |
input power | kw | 40.35 |
power supply | 3PH~380V/50HZ | |
refrigerant | type | R22 |
type of control | thermostatic expansion valve | |
compressor | type | hermetic scroll |
power(kw) | 17.1*2 | |
condenser | type | finned copper tube + low noise outer rotor fan |
cooling air flow(m3/h) | 40000 | |
evaporator | type | tank with coil |
chilled fluid flow(m3/h) | 18.87 | |
volume(L) | 580 | |
inlet and outlet pipe diameter (inch) | 3 | |
pump | power(kw) | 3.75 |
lift(m) | 22 | |
safety protection | compressor over temperature, over current, high and low pressure, over temperature,flow switch, phase sequence, phase-missing, exhaust overheating, antifreezing | |
weight | kg | 1350 |
dimension | mm | 2000*1560*1880 |
Note: 1. Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 12°C
Outlet chilled fluid temperature: 7°C
Inlet cooling air temperature: 30°C
Outlet cooling air temperature: 35°C
2. Working range:
The temperature range of chilled fluid is from 5°C to 35°C;
Temperature difference between inlet and outlet chilled fluid is from 3°C to 8°C.
The machine should be used while the ambient temperature at or below 35°C.