Anges CE water cooled screw Chillers
Water cooled Screw Chillers are welcomed both at home and abroad,such as the European market,the middle east , Southeast Asia
Screw type water chillers adopt the world famous brand compressor-HANBELL and BITZER which obtained several patents from countries of Europe and America and passed the international quality certification of ISO9001.
Technical Parameters of ANGES Srew Type Water Chillers (Air Cooled) with Single Compressor
Model Item | AGS-180ASH | AGS-200ASH | AGS-220ASH | ||||
nominal cooling capacity | kcal/h | 430000 | 490200 | 533200 | |||
kw | 500 | 570 | 620 | ||||
input power | kw | 158 | 183 | 201 | |||
max. running current | A | 395 | 454 | 493 | |||
power supply | 3PH~380V 50HZ | ||||||
refrigerant | type | R22 | |||||
refrigerating circuit | 1 | ||||||
type of control | thermostatic expansion valve | ||||||
compressor | type | semi-hermetic screw | |||||
quantity | 1 | ||||||
start-up mode | Y- | ||||||
capacity control | 0-25-50-75-100 | ||||||
condenser | type | air cooled type finned copper tube | |||||
power (kw) | 15 | 18 | 21 | ||||
cooling air flow (m3/h) | 180000 | 210000 | 235000 | ||||
evaporator | type | shell and tube | |||||
quantity | 1 | ||||||
chilled fluid flow(m3/h) | 86 | 98 | 107 | ||||
inlet and outlet pipe diameter (inch) | 6 | ||||||
safety protection | compressor over temperature, over current, high and low pressure, over temperature,flow Switch, phase sequence, phase-missing, exhaust overheating, antifreezing | ||||||
net weight | kg | 4500 | 4800 | 5300 | |||
running weight | kg | 4900 | 5300 | 5800 | |||
Note: 1. nominal cooling capacity is according to: Inlet chilled fluid temperature: 12 Outlet chilled fluid temperature: 7 Inlet cooling air temperature: 35 Outlet cooling air temperature: 45
2. working range: The temperature range of chilled fluid is from 5 to 20; Temperature difference between inlet and outlet chilled fluid is from 3 to 8. Temperature difference between inlet and outlet cooling air is from 8 to 12. The chiller should be used while the ambient temperature at or below 35.